To start the thermal oil furnace, follow these steps:
1. Press the power button on the touch screen to turn on the system.
2. The automatic 20-second pre-purge will begin, during which you should observe the fan startup and monitor the wind pressure gauge parameters.
3. After the pre-purge, the auxiliary heating will automatically ignite, and the main heating will switch on after approximately 15 seconds. The program controller button will turn green, indicating successful ignition. You can also verify ignition through the fire viewing hole on the burner.
4. If ignition fails, the buzzer will alarm, and the system will automatically enter a 20-second post-purge, with the program controller button turning red.
5. Once the post-purge is complete, the system will automatically attempt to ignite again. Note that initial ignition may be weak due to residual air in the gas pipeline, which is normal.
6. If ignition fails repeatedly, it could be due to incorrect opening of the main or auxiliary heating control valves. In this case, contact our technical support hotline for assistance.
After successful ignition, the system will enter the normal working state, allowing the heat transfer oil to be heated and dehydrated as needed.